UNIFIED 3D + 2D BOILER ROOM & HYDRAULIC SEPARATOR SIMULATOR
Regime 1: Balanced Flow (Qp = Qs)
With Hydraulic Separator — 12.0 m³/h Primary = 12.0 m³/h Secondary (Condensing Active)
1. Piping Topology & 3D RuleDECOUPLED
Header Size
Separator D/d3.0D
2. Boiler & Primary Pump
Boiler Supply Setpoint70 °C
Primary Boiler Pump Speed100%
3. Secondary Zone Pumps
Z1 Radiator Loop (55 kPa)100%
Z2 AHU Coil (110 kPa High-Head)100%
Z3 Underfloor/FCU (38 kPa Low)100%
4. Inspection, Valves & Camera
Hydronic & Thermal BalanceBALANCED
Regime 1 (Qp = Qs): Decoupled hydraulic balance achieved.
Primary Flow (Qp)
12.00 m³/h
Sup 70.0°C · Ret 52.5°C
Secondary Flow (Qs)
12.00 m³/h
Sup 70.0°C · Ret 52.5°C
Separator Velocity
0.100 m/s
Limit ≤ 0.15 m/s (Ø206 mm)
Manifold ΔP Conflict
0.0 kPa
Air 99% · Dirt 97%
Delivered Building Heat
240.5 kW
Core Mix: 0.00 m³/h
Condensing Boiler Eff.
91.0%
Condensing (< 54°C Ret)
Secondary Distribution Manifold (3 Zones)
Live Governing Equations
Standards: Caleffi Idraulica Vol. 15 (D = 3d, v ≤ 0.15 m/s), ASHRAE HVAC Systems, EN 12828.
📐 LIVE 2D HYDRONIC P&ID & CFD SCHEMATIC Synced with 3D Boiler Room
For informational & educational purposes only — not for engineering design. Full responsibility rests with the user.